Home      Catalogue      Fan Heaters      Fan heaters with water heater

Fan heaters with water heater

Goods type:

Operating conditions

 Ambient air temperature,°С...................................-10...+40
 relative air humidity at 20oC not more than ,%..................80
  Do not operate a fan heater in:
- in very dusty manufacturing facilities (with dust and other admixtures contentmore than 10 mg/m3)
- in the rooms with condensed moisture and substances aggressive towards carbon steel (acids, alkali), adhesive or fibrous substances (resin, technical fibers, etc.) in the air.
  Hot or overheated water is used as a heater with parameters:
- working pressure is not more than 1.2 MPa;
- temperature is not more than 150оС.
  Quality of feeding water should correspond to the all-Russian State Standard 20995-75 and SNiP 36-76
  In indicating fan heaters with water heat source, heat rating at water temperature (inlet/outlet) 150oC/130oC and room air temperature +15oC is shown.

 

 

Connection dimensions of coolant inlet/outlet tube:
KEV-25Т3W2, KEV-34Т3,5W2, KEV-30Т3W3, KEV-40Т3,5W3 - 3/4",
KEV-36Т3W2, KEV-49Т3,5W2, KEV-56Т4W2, KEV-60Т3,5W3, KEV-69Т4W3 - 1",
KEV-86Т4W2, KEV-106Т4,5W2, KEV-120Т5W2, KEV-107Т4W3, KEV-133Т4,5W3, KEV-151Т5W3, KEV-180Т5,6W3 - 1 1/4".

Heat parameters are given at indoors air temperature +15°C

Pressure fall value is estimated for water temperature 95/70°C.
This value is multiplied over the coefficient K for other temperatures.

 

Inlet/outlet water temperature, °C 150/70 130/70 105/70 80/60 60/40
К 0,93 0,95 0,98 1,04 1,12

 

 

 

 

 

 

 Control panel

In order to switch over air consumption modes, a fan heater is equipped with a control panel.

If a fan heater is chosen correctly and there is a mixing unit, the control panel allows keeping the predetermined room temperature.

One control panel may controlsimilar fan heaters only, at up to 3A of total current through a control panel.
 

   

* without considering outstanding nipples
** the size with mounting
** mains supply voltage 400 V

Title Air consumption m3/h **** 150/170 **** 130/70 **** 105/70 **** 95/70 **** 80/60 **** 60/40 ***** 150/70 ***** 130/70 ***** 105/70 ***** 95/70 ***** 80/60 ***** 60/40 Overall dimension*, mm Weight (without water), kg Acoustic pressure at 5 m. distance, dB(A) Maximum Current, A Input Power, Watt
KEV-25T3W2 600/ 900/ 1200 7,6/33 9,6/38 10,3/40 10,5/40 8,3/35 3,1/22 0,03 0,04 0,08 0,11 0,11 0,04 467х305х400 (635х362х400)** 15 0,45 95 46
KEV-34T3,5W2 950/ 1450/ 1900 12,4/34 13,0/35 13,8/36 14,0/37 11,2/32 3,5/20 0,04 0,06 0,11 0,15 0,15 0,05 467х305х400 (635х362х400)** 16,5 0,68 130 48
KEV-36T3W2 750/ 1150/ 1500 23,4/51 22,2/49 20,6/47 20,0/46 16,1/40 8,7/28 0,08 0,1 0,16 0,22 0,22 0,12 618х360х496 (654х427х496)** 20,5 0,45 95 47
KEV-49T3,5W2 1200/ 1800/ 2400 27,4/48 25,8/46 24/44 23,3/43 18,8/38 10,2/27 0,09 0,12 0,19 0,25 0,26 0,14 618х360х496 (654х427х496)** 22 0,68 130 49
KEV-56T4W2 1500/ 2250/ 3000 31,4/45 29,7/44 27,7/42 26,9/41 21,7/36 11,8/26 0,11 0,14 0,22 0,29 0,29 0,16 618х360х496 (654х427х496)** 22,5 0,75 160 52
KEV-86T4W2 1850/ 2800/ 3700 47,4/52 45/50 41,8/48 40,5/47 32,8/41 17,5/28 0,16 0,21 0,33 0,44 0,44 0,23 855х450х750 (930х536х750)** 39 0,75 160 54
KEV-106T4,5W2 2550/ 3850/ 5100 58,5/49 55,4/47 51,7/45 50,3/44 40,5/38 21,8/27 0,2 0,25 0,4 0,55 0,55 0,29 855х450х750 (930х536х750)** 39,5 1,1 245 56
KEV-120T5W2 3100/ 4650/ 6200 66,2/46 62,7/44 58,5/43 57/42 45,9/36 24,8/27 0,23 0,29 0,46 0,62 0,62 0,33 855х450х750 (930х536х750)** 42,5 2 420 60
KEV-30T3W3 550/ 850/ 1100 17,3/60 16,5/59 15,5/56 15,0/55 12/47 5,8/30 0,06 0,08 0,12 0,16 0,16 0,08 467х305х400 (635х362х400)** 17 0,45 95 45
KEV-40T3,5W3 800/ 1200/ 1600 22,5/55 21,2/54 20/51 19,4/50 15,6/43 7,8/29 0,08 0,14 0,16 0,21 0,21 0,11 467х305х400 (635х362х400)** 18,5 0,68 130 47
KEV-60T3,5W3 1100/1650/2200 37,6/65 35/61 31,9/57 30,5/55 24,6/47 13,6/33 0,13 0,16 0,25 0,33 0,33 0,18 618х360х496(654х427х496)** 24,5 0,68 130 49
KEV-69T4W3 1350/2050/2700 43/61 40,2/58 36,6/54 35,1/53 28,3/45 15,7/32 0,15 0,18 0,29 0,38 0,38 0,21 618х360х496(654х427х496)** 25 0,75 160 51
KEV-107T4W3 1800/2700/3600 73,4/74 67,5/69 60/63 56,4/61 45,5/52 26,7/37 0,25 0,31 0,47 0,62 0,62 0,36 855х450х750(930х536х750)** 45 0,75 160 53
KEV-133T4,5W3 2450/3700/4900 90,9/69 83,7/65 74,4/59 70,6/57 57/49 33,3/35 0,31 0,38 0,58 0,77 0,77 0,45 855х450х750(930х536х750)** 45,5 1,1 245 55
KEV-151T5W3 2950/4450/5900 102,8/66 94,9/62 84,6/57 80,3/55 64,8/47 37,8/34 0,36 0,43 0,66 0,88 0,88 0,51 855х450х750(930х536х750)** 48,5 2 420 59
KEV-180T5,6W3 3800/5700/7600*** 120/61 112/58 100/53 95/51 77/44 45/32 0,42 0,51 0,78 1,04 1,05 0,6 855х450х750(930х536х750)** 50 1,2 630 61